Fenwal 35-630300-017 Ignition Control Board

Fenwal 35-630300-017 Ignition Control Board

Fenwal Controls Inc.
0 Reviews
$0.00
Product Code: 35-630300-017
Currently Unavailable
Fenwal 35-630300-017 24VAC Intermittent Pilot CSA Ignition Control Board - NO LONGER AVAILABLE WITH NO REPLACEMENT. NO LONGER AVAILABLE
24 VAC Microprocessor Based Intermittent Pilot Ignition Control

FEATURES

  • Safe Start and full time flame sensing
  • Custom prepurge and interpurge timings
  • Multiple trials for ignition
  • Mounts on standard 4 in. junction box
  • System diagnostic LED
  • Flame sense test pins
  • Remote flame sense option
  • Automatic reset 1 hour after lockout option

APPLICATIONS

  • Commercial cooking equipment
  • Commercial gas furnaces
  • Unit heaters
  • Water heaters
  • Other applications requiring intermittent pilot

DESCRIPTION

The 35-63 is a 24 VAC intermittent pilot (spark-to-pilot) ignition control. The microprocessor circuit design provides precise, repeatable timing and operating sequences. The on-board diagnostics with LED output make troubleshooting easy and ensures safe and efficient operation.

SPECIFICATIONS

Input PowerControl: 18-30 VAC 50/60 Hz (Class 2 Transformer)
Input Current Drain300 mA@24 VAC with gas and pilot relays energized (Control only)
Main Gas Valve 2.0Amax (continuous)
Pilot Gas Valve2.0Amax (continuous)
Operating Temperature-40F to +176F (-40C to +80C)
Storage Temperature-40F to +185F (-40C to +85C)
Flame Sensitivity 0.7 uAminimum
Flame Failure Response Time 0.8 seconds maximum
Types of GasesNatural, LP, or manufactured
Spark RateLine frequency (50/60 sparks/sec)
Size (LxWxH)5.69 x 3.94 x 1.87 inches (with cover) 14.45 x 10.01 x 4.75 cm (with cover)
Weight8 ounces (nominal) 224 grams (nominal)
Moisture ResistanceConformal coated to operate non-condensing to 95% R.H. Care must be taken to protect module from direct exposure to water
Tries for IgnitionOne or three try versions available
Trial for Ignition Periods15, 30, 60, 90 seconds available
Prepurge TimingsNone, 15, 30, 45 seconds or 4 minutes available
Interpurge TimingsNone, 15, 30, 45 seconds, or 4 minutes available

CONTROL CONFIGURATION

Options

Special European Model*

Enclosure Configurations and Wiring Options

Noryl Gray Enclosure

Number of Ignition Trials, Flame Sense Method and Lock Out Reset Method

Single Try, Local Sense Thermostat / power off reset

Pre-Purge Time

None

Inter-Purge Time

15 seconds

Trial for Ignition Time (TFI)

90 seconds