Ignition Control Module Mighty Therm Ignition Control Module Electronic Spark & Standing Pilot,
Natural/LP, CSD-1, (100% Lockout), G770 (prior to S/N C02F04751) G770-KGA-3, G770 KGA-3
Replaces the following Johnson Ignition Controls.
G770KGA-3
APPLICATIONS The Fenwal 35-63J series Intermittent Pilot Ignition Control (35- 63J) is a microprocessor based ignition control suitable for replacing many existing intermittent pilot ignition controls from various manufacturers. The 35-63J is a direct form, fit, and functional replacement for the discontinued Johnson G77x series controls. The 35-63J is available in a number of timing configurations that match popular G77x applications providing a better solution than a universal type aftermarket control. The 35-63J is suitable for many types of heating applications including commercial cooking, furnaces, boilers, and water heaters that require intermittent pilot ignition, burner supervision through flame rectification, and safety shutoff. It is designed for use with Natural, LP, and mixed gases used in gas-fired appliances. The microprocessor circuit design of the 35-63J provides precise, repeatable timing and operating sequences. High energy spark output and excellent flame sense characteristics provide reliable burner operation. The on-board diagnostics with LED output make troubleshooting easy and ensure safe and efficient operation. FEATURES - Safe start and full-time flame sensing - Wide variety of prepurge and interpurge timings - Single or three trials for ignition - Diagnostic LED with Fenwal error codes - Three ground terminals for ease of wiring - Remote or local flame sense options - Automatic 5 min or 1 hour reset after lockout options. 9July11cr
This Ignition Module is used on the following models:
AP0500 * AP0600 * AP0715 * AP0850 * AP0999 * AP1010 * AP1200 * AP1430 * AP1670 * AP1825 * AP1999 AP2000 * AP2200 * AP2450 * AP2800 * AP3050 * AP3200 * AP3500 * AP3600 * AP4000 * AP4050 * AP4500 AP5000 * HH0500 * HH0600 * HH0715 * HH0850 * HH1010 * HH1200 * HH1430 * HH1670 * HH1825 * HH2000 HH2200 * HH2450 * HH2800 * HH3050 * HH3200 * HH3500 * HH3600 * HH4000 * HH4050 * HH4500 * HH5000 IW0500 * IW0600 * IW0715 * IW0850 * IW1010 * IW1200 * IW1430 * IW1670 * IW1825 * MT0500 * MT0600 * MT0715 * MT850 * MT1010 * MT1200 * MT1430 * MT1670 * MT1825 * MT2000 * MT2200 * MT2450 * MT2800 * MT3050 * MT3200 * MT3500 * MT3600 * MT4000 * MT4500 * MT5000 * PH0500 * PH0600 * PH0715 * PH0850 * PH1010 * PH1200 * PH1430 * PH1670 * PH1825 * PH2000 * PH2200 * PH2450 * PH2800 * PH3050 * PH3200 * PH3500 * PH3600 * PH4000 * PH4050 * PH4500 * PH5000 * PW0500 * PW0600 * PW0715 * PW0850 * PW1010 * PW1200 * PW1430 * PW1670 * PW1825 * PW2000 * PW2200 * PW2450 * PW2800 * PW3050 * PW3200 * PW3500 * PW3600 * PW4000 * PW4050 * PW4500 * PW5000 * VW0500 * VW0600 * VW0715 * VW0850 * VW1010 * VW1200 * VW1430 * VW1670 * VW1825 * VW2000 * VW2200 * VW2450 * VW2800 * VW3050 * VW3200 * VW3500 * VW3600 * VW4000 * VW4050 * VW4500 * VW5000
Mighty Therm, Ignition Control Kit, E2033900 Electronic Spark & Standing Pilot, Natural/LP, CSD-1, (100% Lockout), G770 (prior to S/N C02F04751, 500-1825
Input Power Control: 24 VAC 50/60 Hz (Class 2 Transformer)
Input Current Drain 200 mA @ 24 VAC with gas and pilot relays energized (Control only)
Maine Gas Valve 2.0A max (continuous)
Pilot Gas Valve 2.0A max (continuous)
Operating Temperature -40 deg. F to + 176 deg. F (-40 deg. C to +80 deg. C)
Storage Temperature -40 deg. F to + 185 deg. F (-40 deg. C to +85 deg. C)
Flame Sensitivity 0.3 μA minimum
Flame Failure Response, Recycle After Loss of Flame (hard reset)
Flame Detector Self-check Rate, Once per second minimum
Flame Failure Lockout Time Varies by model, 500 seconds maximum
Types of Gas Natural, LP, or manufactured
Spark Rate, Remote sense (50/60 Hz), Local sense (25/30 Hz)
Physical Size (L x W x H) 4.70 x 3.10 x 2.50 inches, (11.94 x 7.87 x 6.35 cm)
Moisture Resistance, Conformal coated to operate non-condensing to 95% R.H.
Tries for Ignition, 1 = Single Try, Remote Sense. Thermostat / power off reset
Trial for Ignition Period, 8 seconds.
Pre-purge 0 seconds.
Inter-purge Timing, 15 seconds.
|