Fenwal 35-673902-561 Ignition Control 24 VAC Proven HSI W/Blower Relay

Fenwal 35-673902-561 Ignition Control 24 VAC Proven HSI W/Blower Relay

Fenwal Controls Inc.
0 Reviews
$0.00
$337.64
You save $0.00!
Product Code: 35-673902-561
Fenwal 35-673902-561 Ignition Control 24 VAC Proven HSI W/Blower Relay

***THIS CONTROL IS NO LONGER AVAILABLE, YOU WILL RECEIVE A FACTORY DIRECT REPLACEMENT***
24 VAC Proven Hot Surface Ignition Control with Combustion Blower Relay Microprocessor Based

FEATURES

  • Proven pressure switch input
  • Combustion fan output
  • 24/120/240 VAC hot surface ignitor models available
  • ASME CSD-1 compatible models available (consult factory)
  • Pre-purge and lockout indicator outputs
  • Diagnostic LED
  • Multiple trials for ignition
  • Thermostat, pushbutton or remote reset
  • Remote diagnostic LED
  • Remote flame sensor option
  • Flame current test pins
?

APPLICATIONS

Commercial and industrial appliances with combustion chambers in excess of 400K BTU. Applications requiring CSD-1 certification.

?

DESCRIPTION

The Series 35-67 is a hot surface ignition system in which the ignition source is proven to be capable of ignition prior to the gas valve being opened and is suitable for appliances over 400K BTU. Models compatible to the requirements of ASME standard CSD-1 are available.

The microprocessor circuit design provides precise, repeatable timing sequences for ignition times and purge times (pre-, inter-, and post-) as well as multiple tries for ignition. The control also continuously monitors the pressure switch, thermostat and main burner flame to ensure safe system operation. On-board diagnostics with LED output provide assistance with troubleshooting to ensure safe and efficient burner operation.

???

SPECIFICATIONS

INPUT VOLTAGESDESCRIPTION
Control18 to 30 VAC, 400mAmax (not including gas valve)
Line24/120/240 VAC (L1 & L2 only, voltage depends on model)
Thermostat18 to 30 VAC 30mAmax (incl. Gas Valve)
Pressure Switch18 to 30 VAC 25mAmax
Hot Surface Element24/120/240 VAC 5Amax
Output Ratings
Inducer FanRelay: 15Amax or 1/3HP @ 120 or 240 VAC
Hot Surface Element5.0Amax @ 24, 120 or 240 VAC
Gas Valve Rating5.0Amax @ 24 VAC
Lockout & Pre-Purge Indicators1.0Amax @ 24 VAC
Operating Temperature-40F to +165F (-40C to +73C)
Flame Sensitivity4.0mAminimum
Flame Failure Response Time0.8 seconds max
Types of GasNatural, LP, or manufactured
Ignitor24 VAC, 120 VAC, or 240 VAC mini-ignitors and silicon carbide ignitors depending on model
Enclosure Gray (Noryl N-190)
Moisture ResistanceConformal coated to operate non-condensing to 95% R.H. Care must be taken to protect module from direct exposure to water
Size with enclosure See Figures 6 & 7
Weight8oz including options and cover

CONTROL CONFIGURATION

Other Features

Indicators and Inducer

Proven Pressure Switch, Full Time Power, Termination

Special OEM Features (Consult Factory for Special Number)

Dwell Time

4 Seconds

Tries For Ignition

Single Try - Local Sense. Lockout On Flame Loss

Purge Timing

15 Prepurge, 15 Interpurge, 30 Postpurge (Full Time Power)

Proving Current (Amps)

3.1

Trial for Ignition

4 Seconds