• Get Your Parts Fast! Place your order before 4PM EST and it will ship on the same or next business day.

Navigate to the parts4heating.com homepage

CALL 800-536-1582

For a faster response Email Us

Johnson Controls G770KGA-3 Ignition Control Module
Johnson Controls G770KGA-3 Ignition Control Module - Image 1 of 0
Johnson Controls G770KGA-3 Ignition Control Module - Image 2 of 0
Johnson Controls G770KGA-3 Ignition Control Module - Image 1 of 0
Johnson Controls G770KGA-3 Ignition Control Module - Image 2 of 0
Johnson Controls G770KGA-3 Ignition Control Module - Image 1 of 0
Johnson Controls G770KGA-3 Ignition Control Module - Image 2 of 0

Johnson Controls G770KGA-3 Ignition Control Module, Fenwal direct replacement

Johnson
0 Reviews
$0.00
$270.84
You save $0.00!
Product Code: G770KGA-3
Ignition Control Module Mighty Therm Ignition Control Module Electronic Spark & Standing Pilot,
Natural/LP, CSD-1, (100% Lockout), G770 (prior to S/N C02F04751) G770-KGA-3, G770 KGA-3

Replaces the following Johnson Ignition Controls.

G770KGA-3

APPLICATIONS
The Fenwal 35-63J series Intermittent Pilot Ignition Control (35-
63J) is a microprocessor based ignition control suitable for
replacing many existing intermittent pilot ignition controls from
various manufacturers.
The 35-63J is a direct form, fit, and functional replacement for
the discontinued Johnson G77x series controls. The 35-63J is
available in a number of timing configurations that match popular
G77x applications providing a better solution than a universal
type aftermarket control.
The 35-63J is suitable for many types of heating applications
including commercial cooking, furnaces, boilers, and water
heaters that require intermittent pilot ignition, burner supervision
through flame rectification, and safety shutoff. It is
designed for use with Natural, LP, and mixed gases used in
gas-fired appliances.
The microprocessor circuit design of the 35-63J provides precise,
repeatable timing and operating sequences. High energy
spark output and excellent flame sense characteristics provide
reliable burner operation. The on-board diagnostics with LED
output make troubleshooting easy and ensure safe and efficient
operation.
FEATURES
- Safe start and full-time flame sensing
- Wide variety of prepurge and interpurge timings
- Single or three trials for ignition
- Diagnostic LED with Fenwal error codes
- Three ground terminals for ease of wiring
- Remote or local flame sense options
- Automatic 5 min or 1 hour reset after lockout options.
9July11cr


This Ignition Module is used on the following models:

AP0500 * AP0600 * AP0715 * AP0850 * AP0999 * AP1010 * AP1200 * AP1430 * AP1670 * AP1825 * AP1999
AP2000 * AP2200 * AP2450 * AP2800 * AP3050 * AP3200 * AP3500 * AP3600 * AP4000 * AP4050 * AP4500
AP5000
* HH0500 * HH0600 * HH0715 * HH0850 * HH1010 * HH1200 * HH1430 * HH1670 * HH1825 * HH2000 HH2200 * HH2450 * HH2800 * HH3050 * HH3200 * HH3500 * HH3600 * HH4000 * HH4050 * HH4500 * HH5000 IW0500 * IW0600 * IW0715 * IW0850 * IW1010 * IW1200 * IW1430 * IW1670 * IW1825 * MT0500 * MT0600 * MT0715 * MT850 * MT1010 * MT1200 * MT1430 * MT1670 * MT1825 * MT2000 * MT2200 * MT2450 * MT2800 * MT3050 * MT3200 * MT3500 * MT3600 * MT4000 * MT4500 * MT5000 * PH0500 * PH0600 * PH0715 * PH0850 * PH1010 * PH1200 * PH1430 * PH1670 * PH1825 * PH2000 * PH2200 * PH2450 * PH2800 * PH3050 * PH3200 * PH3500 * PH3600 * PH4000 * PH4050 * PH4500 * PH5000 * PW0500 * PW0600 * PW0715 * PW0850 * PW1010 * PW1200 * PW1430 * PW1670 * PW1825 * PW2000 * PW2200 * PW2450 * PW2800 * PW3050 * PW3200 * PW3500 * PW3600 * PW4000 * PW4050 * PW4500 * PW5000 * VW0500 * VW0600 * VW0715 * VW0850 * VW1010 * VW1200 * VW1430 * VW1670 * VW1825 * VW2000 * VW2200 * VW2450 * VW2800 * VW3050 * VW3200 * VW3500 * VW3600 * VW4000 * VW4050 * VW4500 * VW5000
Input Power Control: 24 VAC 50/60 Hz (Class 2 Transformer)

Input Current Drain 200 mA @ 24 VAC with gas and pilot relays energized (Control only)

Maine Gas Valve 2.0A max (continuous)

Pilot Gas Valve 2.0A max (continuous)

Operating Temperature -40F to + 176F (-40C to +80C)

Storage Temperature -40F to + 185F (-40C to +85C)

Flame Sensitivity 0.3 μA minimum

Flame Failure Response, Recycle After Loss of Flame (hard reset)

Flame Detector Self-check Rate, Once per second minimum

Flame Failure Lockout Time Varies by model, 500 seconds maximum

Types of Gas Natural, LP, or manufactured

Spark Rate, Remote sense (50/60 Hz), Local sense (25/30 Hz)

Physical Size (L x W x H) 4.70 x 3.10 x 2.50 inches, (11.94 x 7.87 x 6.35 cm)

Moisture Resistance, Conformal coated to operate non-condensing to 95% R.H.

Tries for Ignition, 1 = Single Try, Remote Sense. Thermostat / power off reset

Trial for Ignition Period, 8 seconds.

Pre-purge 0 seconds.

Inter-purge Timing, 15 seconds.